HP to Amps Calculator

Estimate the current a motor draws from its horsepower, voltage, efficiency and power factor — for DC, single-phase and three-phase motors — and look up the NEC full-load current used for code sizing.

HP presets
Voltage presets
PF presets

HP to amps formulas

P_out (W) = hp × 745.7 DC: I = hp × 745.7 / (V × η) AC single-phase: I = hp × 745.7 / (V × η × PF) AC three-phase: I = hp × 745.7 / (√3 × V × η × PF)

Motor horsepower is mechanical output. Electrical input is larger by the efficiency η (typically 0.75–0.85 for small single-phase motors and 0.88–0.96 for three-phase industrial motors). AC motors also draw reactive current, captured by the power factor PF (about 0.7–0.9 at full load). One mechanical horsepower = 745.7 W.

Worked examples

Three-phase: 10 hp, 460 V, η = 90%, PF = 0.85: I = 7457 / (1.732 × 460 × 0.90 × 0.85) = 12.2 A. NEC Table 430.250 lists 14 A — the table is deliberately conservative.

Single-phase: 2 hp, 230 V, η = 80%, PF = 0.85: I = 1491.4 / (230 × 0.80 × 0.85) = 9.54 A (NEC Table 430.248: 12 A).

DC: 1 hp, 90 V, η = 80%: I = 745.7 / (90 × 0.80) = 10.4 A.

NEC Table 430.248 – single-phase motor full-load current (A)

HP115 V200 V208 V230 V
1/64.42.52.42.2
1/45.83.33.22.9
1/37.24.14.03.6
1/29.85.65.44.9
3/413.87.97.66.9
1169.28.88.0
1-1/22011.511.010
22413.813.212
33419.618.717
55632.230.828
7-1/28046.044.040
1010057.555.050

NEC Table 430.250 – three-phase induction motor full-load current (A)

HP200 V208 V230 V460 V575 V
1/22.52.42.21.10.9
3/43.73.53.21.61.3
14.84.64.22.11.7
1-1/26.96.66.03.02.4
27.87.56.83.42.7
311.010.69.64.83.9
517.516.715.27.66.1
7-1/225.324.222119
1032.230.8281411
1548.346.2422117
2062.159.4542722
2578.274.8683427
309288804032
401201141045241
501501431306552
601771691547762
752212111929677
10028527324812499
125359343312156125
150414396360180144
200552528480240192

Values from NFPA 70 (NEC) Tables 430.248 and 430.250, unchanged across the 2017–2023 editions. Currents are permitted for system voltages of 110–120, 220–240, 440–480 and 550–600 V. Squirrel-cage and wound-rotor induction motors at usual belted-motor speeds.

Calculated current vs. NEC table current

NEC 430.6(A)(1) requires the table full-load current, not the nameplate or a calculated value, for sizing branch-circuit conductors (125% per 430.22), short-circuit and ground-fault protection, and disconnects. The motor nameplate current is used for overload protection (430.32). Use the calculator for estimates, energy studies and non-NEC work; use the tables for code sizing.

Frequently asked questions

How many amps does a 1 hp motor draw?

From NEC Table 430.248, a 1 hp single-phase motor is 16 A at 115 V and 8 A at 230 V. A 1 hp three-phase motor is 4.2 A at 230 V and 2.1 A at 460 V (Table 430.250).

How do I convert HP to amps?

Multiply horsepower by 745.7 to get watts, divide by efficiency, then divide by voltage (DC), by voltage × power factor (single-phase), or by √3 × voltage × power factor (three-phase).

Why is the NEC table higher than my calculation?

The NEC tables are conservative values intended to cover typical motors of that rating, including lower-efficiency and lower-power-factor designs, so conductors and protection are not undersized.

What efficiency and power factor should I use?

Use the nameplate if available. Otherwise about 85–92% efficiency and 0.85 PF for three-phase motors over 5 hp, and 70–80% efficiency with 0.75–0.85 PF for small single-phase motors.

How many amps is a 10 hp 3-phase motor?

NEC Table 430.250: 30.8 A at 208 V, 28 A at 230 V, 14 A at 460 V and 11 A at 575 V.